The EXL is a wall mounted system that monitors and controls a single engine generator for in parallel with a single utility source. This cost effective alternative to switchgear mounted controls is designed for voltages from 208V – 32kV. The EXL will support Emergency Standby as well as Utility Paralleling.

SPECIFICATIONS

ConfigurationWall mounted paralleling control system that monitors and controls a single generator and a single utility.

Modes of OperationUtility Import, Export, and base load operations, Peak shaving, and Emergency Standby. Closed Transition to/from Generator Power

ApplicationLV and MV (208V-32kV)

technical summary

ConfigurationWall mounted paralleling control system that monitors and controls a single generator and a single utility.

Modes of OperationUtility Import, Export, and base load operations, Peak shaving, and Emergency Standby. Closed Transition to/from Generator Power

ApplicationLV and MV (208V-32kV)

generator protective devices

ANSI Protective Devices15/25. 27/59, 81 O/U, 32, 40, 50, 51

utility protective devices

ANSI Protective Devices15/25. 27/59, 81 O/U, 32, 40, 47, 51, 86

environmental parameters

CertificationsIBC, CBC, UBC,

oshpd certified

Environmental ParametersControl Panel Enclosure

nema 1 or nema 3r freestanding construction

Environmental ParametersOperating Temperature

050°c

Environmental ParametersStorage Temperature

20°c to +60°c

Environmental ParametersLow Voltage Standards

nema sg5 csaansi c3751 ansi c37201 ul1558 or ul 891 nfpa 110 nfpa 99 and nfpa 70

Environmental ParametersMedium Voltage Standards

nema sg5 ansi ieee c37202 csac222 no 31m89 eemac g832 nfpa 70 nfpa 99 and nfpa 1110

Emergency Transfer Load Manager (EXL) STANDARD EQUIPMENT

  • 6" lcd touchscreen display hmi
  • instant auto selector switch
    Allows user to return sysem to automatic in the event of a touchscreen failure
  • spare inputs and outputs
    3 digital inputs and 6 relay outputs programmable from the HMI
  • top or bottom interconnect control wiring access

Emergency Transfer Load Manager (EXL) OPTIONS

    • supplemental hardware 25 device
      Provides additional discrete synchronization protection