SPECIFICATIONS

ConfigurationTraditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads

Modes of OperationEmergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power

ApplicationLV and MV ( 208V - 38 kV

technical summary

ConfigurationTraditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads

Modes of OperationEmergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power

ApplicationLV and MV ( 208V - 38 kV

generator protective devices

ANSI Protective Devices15/25, 27/59, 81 O/U, 32, 40, 50, 51

utility protective devices

ANSI Protective Devices15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86

environmental parameters

CertificationsIBS, CBC, UBC

oshpd certified

Environmental ParametersControl Panel Enclosure

nema 1 or nema 3r freestanding construction

Environmental ParametersOperating Temperature

0 degrees to 50 degrees c

Environmental ParametersStorage Temperature

20 degrees c to +60 degrees c

Environmental ParametersLow Voltage Standards

nema sg5 csa ansi c3751 ansi c37201 ul 1558 or ul 891 nfpa 110 nfpa 99 and nfpa 70

Environmental ParametersMedium Voltage Standards

nema sg5 ansi ieee c37202 csac222 no 31m89 eemac g832 nfpa 70 nfpa 99 and nfpa 1110

Cat XLM Switchgear STANDARD EQUIPMENT

  • choice of 19” surface acoustic wave color or 15” resistive color touchscreen
  • user selected multifunction relay utility grade
  • circuit breaker control switch withindicators
  • audible alarm
    Horn Silence Button

  • Emergency Stop Button for eachgenerator

  • Instant Auto Switch to Return System to Ready State

  • Generator Demand Priority Control
  • automatically match the online generator capacity to the loads and avoid unnecessary operation of generator sets

Cat XLM Switchgear OPTIONS

    • redundant touchscreens
    • redundant communication networks
    • ats and ups communication
      Display

    • Data Table Interface
    • accommodates interface with a building management system for monitoring all system parameters via modbus rtu or tcp
      Historical Trending (19” Touchscreen)

    • Remote Event Notification

    • Utility Interconnect Multi-function Relay (Utility Grade)

    • Supplemental Hardware Synchronization check relay (ANSI 25 Device)
    • provides additional discrete synchronization protection
      Remote Power Monitoring System
    • to monitor breaker status alarms metering and other operating parameters
      Distribution Breaker monitoring and control NFPA Compliant JCAHO Reporting

    • Long Term Historical Trending