JA Delmas

LEGAL NOTICE & CREDITS © 2024 Burkina Equipements

JA Delmas

HOME BRANDS & PRODUCTS CAT PRODUCT LINE POWER SYSTEMS ELECTRIC POWER GENERATION RENTAL GENERATOR SETS XQ2000

XQ2000

Back to the list

SPECIFICATIONS

Continuous Rating1400 ekW (1750 kVA)

Prime Rating1600 ekW (2000 kVA)

Voltage400/240 V

BENEFITS AND FEATURES

generator

Continuous Rating1400 ekW (1750 kVA)

Prime Rating1600 ekW (2000 kVA)

Voltage400/240 V

Frequency50 Hz

Frame Size826

Pitch0.6667

No. of poles4

ExcitationStatic regulated brushless PM excited

ConstructionsDouble bearing, close coupled

InsulationClass H

EnclosureDrip proof IP22

AlignmentPilot shaft

Overspeed capability – % of rated125% of rated

Voltage regulator3 phase sensing with Volts-per-Hertz

Voltage regulationLess than ± 0.5% voltage gain; Adjustable to compensate for engine speed droop and line loss

Wave form deviationLess than 5% deviation

Telephone Influence Factor (TIF)Less than 50

Harmonic Distortion (THD)Less than 5%

engine

CAT 3516B Flex-Fuel Engine3516B, 4-Stroke diesel

Bore170 mm

Stroke190 mm

Displacement69 L

Compression ratio15:1

AspirationTA

Fuel systemEUI

Governor typeCat ADEM A4 Control System

EmissionsNon-Certified

dimension

Width (without Chassis / with Chassis)2438 mm

Height (without Chassis)2896 mm

Height (w/Chassis)4267 mm

Length (without Chassis / with Chassis)12192 mm

Weight (without Chassis) (w/lube oil and coolant)29021 kg

Weight (w/Chassis) (w/lube oil and coolant)33638 kg

BENEFITS AND FEATURES

XQ2000 - DGB STANDARD EQUIPMENT

  • engine
    Cat 3516B heavy duty flex fuel engine
    Heavy duty, single element canister type air cleaner with service indicator
    Fuel filters – primary and duplex secondary with integral water separator and change-over valve
    Spin on, full flow oil filters with water cooled oil cooler. Requires API CF-4 lube oil
    Stainless Steel Aftercooler core
    Jacket water heater, 9kW, 400V, 50 Hz, 3-phase w/isolation valves
    Fuel cooler and priming pump
    Electronic ADEM™ A4 controls
    Integrated Sensor Module (ISM) for combustion sensing and exhaust gas sensing
    Dual 24V electric starting motors
  • generator
    Double bearing SR-4B brushless, form wound, permanent magnet excited, three-phase with Cat digital voltage regulator (Cat DVR), space heater, 6-lead design, Class H insulation operating at Class F temperature for extended life, winding temperature detectors and anti-condensation space heaters (120/240V 1.2 kW).
    Generator equipped with System 4 insulation protection.
  • containerized module
    40' ISO high cube container, 9-High stack CSC certified
    Four (4) sound attenuated air intake louvers and 3 lockable personnel doors with panic release
    Interior walls and ceilings insulated with 100 mm of acoustic paneling
    Floor of container insulated with acoustic glass and covered with galvanized steel
    Side bus bar access door, external access load connection bus bars
    Shore power connection via distribution block connections for jacket water heater, battery charger, space heaters, and generator condensate heaters
    Six (6) DC lights
    1,250 gal fuel tank, UL listed, double wall, >13 hr runtime @ Continuous rating
    Solenoid diesel fuel fill control valve
    Lube oil level regulator with makeup tank
    Sound attenuated 75 dB(A) @ 15 m (50 ft)
    Four (4) oversized maintenance-free batteries, battery rack and 20-Amp battery charger
    Critical grade exhaust silencer with dual 2 m (6.5 ft.) exhaust stacks for increased site power density
    Vibration isolators, stainless steel fastening hardware and hinges
    External drain access to standard fluids
    One 4.5 kg (10lb) carbon dioxide fire extinguisher
    Standard Cat rental decals and painted standard Cat power module white
    110% spill containment system for on-board engine fluids
    Methane Leak Detection
  • gaseous fuel system
    Low pressure regulator
    Electronically actuated fuel control valve
    Gaseous fuel heater
    Electronically controlled gas shut-off valve
    Gas induction nozzles
    1 micron gas fuel filter with dP sensors and isolation ball valve with 1” BSP drain plug for fluid build-up
    CSA certified gas electronic components
  • cooling
    Standard cooling provides 43C (110F) ambient capability at 100% Prime
    Horizontally mounted radiator with vertical air discharge
    Variable frequency fan drive (VFD) for optimal partial load fuel consumption
  • generator controls and protection
    Controls provide auto paralleling AGC-4 controller, voltage and frequency adjust, base load / PF / load sharing / synchronizer, auto start / stop control
  • generator cb control scada interface ethernet fuel level indications
    alarms, fuel tank fuel transfer control
    EMCP 4.3 genset mounted controller
    Automatic start/stop with cool down timer
    Generator Protection features: 25, 32, 40, 50/51, 27/59, 81 O/U
    Reverse compatibility for interface to legacy power modules
    3000A UL rated generator circuit breaker with LSIG trip unit w/ammeter
    Multi-mode operation (island, multi-island and utility parallel), load sharing (multi-unit only)
    Manual and automatic paralleling capability
    Metering display: voltage, current, frequency, power factor, kW, WHM, kVAR, and synchroscope
  • quality
    Factory testing of standard generator set and complete power module
    UL, NEMA, ISO and IEEE standards
    O
  • m manuals
    EMCP 4.3 Local Control Panel
  • generator mounted emcp 43 provides power metering protective relaying and engine and generator control and monitoring###convenient service access for cat service tools not included###integration with the cat dvr provides enhanced system monitoring###ability to view and reset diagnostics of all controls networked on j1939 datalink eliminates need for separate service tools for troubleshooting###realtime clock allows for date and timestamping of diagnostics and events###customer communication through modbus tcp###true rms ac metering 3 phase ll volts ln volts phase amps hz ekw kva kvar kwhr % kw pf
    EMCP 4.3 Engine Operator Interface
  • graphical display with positive image transflective lcd adjustable white backlightcontrast###digital indication for
    • rpm
    • dc volts
    • operating hours
    • oil pressure
    • coolant temperature
    • oil temperature
    • gas pressure
    • gas substitution %
    • gas shutoff valve status
    • dgb activation
      • ###two led status indicators 1 red 1 amber###engine cooldown timer###engine cycle crank###three engine control keys and status indicators runautostop###lamp test and alarm acknowledgement keys###warningsshutdowns with indicating text for
        • low oil pressure
        • overspeed
        • high oil temperature
        • overcrank
        • emergency stop
        • agc4
          • ###emergency stop pushbutton###display navigation keys including two shortcut keys for engine parameters or generator parameters

    Container
  • 40’ iso high cube container csc 9high stack certified###painted standard cat power module white per caterpillar specifications###standard air intake louvers###three 3 lockable personnel doors with panic release###fire extinguisher###110% spill containment system for onboard engine fluids
    AGC-4/EMCP 4.3 Protective Relaying
  • generator protective features
    • 25 synccheck agc4
    • 32 rev power emcp 43 and agc4
    • 40 loss of excitation cat dvr and agc4 impedance based
    • 5051 inst and time overcurrent gcb trip unit and agc4
    • 47 negative voltage sequence agc4
    • 46 negative sequence current agc4
    • 2759 phase underover voltage emcp 43 and agc4
    • 81ou underover frequency emcp 43 and agc4
      • ###package mounted agc4 controls provides auto paralleling canbus ethernet communications pwm and analog outputs and legacy analog load sharing real and reactive ###agc4 main display aop secondary display

    Voltage Regulation and Power Factor Control Circuitry
  • generator mounted automatic voltage regulator microprocessor based###manual raiselower voltage adjust capability and varpower factor control circuitry all via agc 4 for maintaining constant generator power factor while paralleled with utility###includes rfi suppression exciter limiter and exciter diode monitoring
    Current Transformers
  • ct’s rated 30005 with secondaries wired to shorting terminal strips
    Circuit Breaker
  • 3000a fixed type 3 poles genset mounted electrically operated insulated ul489 cb###solid state trip unit for overload time overcurrent and fault instantaneous overcurrent protection lsig is standard###includes dc shunt trip coil activated on any monitored engine or electrical fault 100 kainterrupting capacity at 480 vac###undervoltage release 24vdc###optional external ground fault sensingtrip requires additional ground ct
    Internal Lighting
  • six 6 internal 24vdc led lights with timers located at the control area personnel door###one 1 duplex service receptacle
    Battery Charger and Batteries
  • 24 vdc20a battery charger with floatequalize modes and charging ammeter###four oversized maintenance free batteries
    Emergency Stop Pushbutton
  • single emergency stop pushbuttons esp located on rear face of generator set controls area###emergency stop pushbutton located on the container exterior at each personnel door3
    Exhaust Silencer
  • critical grade internally mounted dual cylindrical exhaust silencers###2 m high vertical discharging exhaust stack located in radiator discharge area
    Fuel Tank
  • ul listed 1250 gallon double walled tank###fuel solenoid valve system###triple fuelwater separators
    Modes of Operation
  • provides for single unit standalone operation island mode paralleling and load sharing with other power modules and single unittoutility mode paralleling for base load control with open transition between paralleling modes*###island mode paralleling features
    • agc4 control allows single unit to connect to a dead bus
    • auto synchronization voltage

    phase matching)
  • Load sharing (kW) analog signal (like units
  • legacy compatible
  • load sharing kvar analog signal like units only
    • ###utility mode paralleling features
      • auto synchronization voltage

  • phase matching)
  • Base-load control (selectable: programmable set-point or potentiometer adjust)
  • Soft load/unload (programmable, shared setpoint)
  • Power Factor control (programmable setpoint)
  • bus bars
    Three phase, plus full rated neutral, bus bars are tin-plated copper with NEMA standard hole pattern for connection of customer load cables and generator cables.
    Bus bars are sized for full load capacity of the generator set at 0.8 power factor.
    Includes ground bus, tin-plated copper, for connection to the generator frame ground and field ground cable.
  • ac distribution
    3 phase, 400VAC, 50 Hz, 50 amp input which can be derived from either the Power Module main output bus (Internal) or customer supplied shore power (External) via selector switch.
    Onboard 50 Hz Transformer for the Power Module AC auxiliaries provides 240/120 VAC for all module accessories except Jacket water heater (400V). Includes controls to de-energize jacket water heaters and generator space heater when the engine is running
  • lube oil makeup system
    Includes oil pan-mounted oil level regulator and 114 L (30 gal) oil tank for maintaining oil pan levels in extended run applications. Oil tank can be remotely filled without shutting down the engine.
  • XQ2000 - DGB OPTIONS

      • trailer
        Three axle with Anti-lock brake system
        Goodyear G314 295/75R225 Load Range G
    Back

    MOTEUR

    • Generator set manufactured in ISO 9001:2000 compliant facility
    • Package factory designed and production tested
    • Generator set and components meet or exceed the following specifications: AS1359, AS2789, BS4999, DIN6271, DIN6280, EGSA101P, JEM1359, IEC 34/1, ISO3046/1, ISO8528, NEMA MG1-22

    BENEFITS AND FEATURES

    Single Source Supplier

    • Cat® dealers provide extensive post sale support including maintenance and repair agreements
    • Supported 100% by your Cat dealer with warranty on parts and labor

    BENEFITS AND FEATURES

    Worldwide Product Support

    • The compact, four-stroke-cycle Cat 3516B turbocharged-aftercooled diesel engine combines durability while providing dependability and economy
    • Stainless steel engine aftercooler core to extend component, oil, and overall engine life when using gaseous fuels with elevated H2S levels
    • Fuel system operates on a variety of gaseous fuels
    • Integral gas train, gas filter, and isolation valve
    • Includes methane detection system and related safeties

    BENEFITS AND FEATURES

    Reliable, Fuel Eficient Diesel Engine

    Cat SR4B 826 frame generator designed to match the performance and output characteristics of the Cat diesel engine
    Double bearing, wye-connected, static regulated, brushless, permanent magnet excited

    BENEFITS AND FEATURES

    Cat Generator

    • 110% spill containment of onboard engine fluids
    • Positive crankcase fumes ventilation

    BENEFITS AND FEATURES

    Reduced Environmental Impact

    • Provides 9-high stack CSC rated enclosure for ease of transportation and protection
    • Meets 75 dB(A) at 15 meters or below per SAE J1074 measurement procedure at prime rating

    BENEFITS AND FEATURES

    Sound Attenuated Container

    • Requires gas inlet pressure range of 5-35 psi (34-241 kPa)
    • Achieves up to 70% substitution, depending on gas quality, while maintaining diesel performance and safe engine operation
    • Closed loop control system enables maximum substitution over the widest load range in the industry
    • Maintains traditional diesel generator set power and transient response performance
    • DGB system, when enabled, can automatically activate when gas supply is detected
    • Accepts a wide range of gas quality and automatically adjusts to fuel quality changes, eliminating the need for field calibration
    • Leverages current hardware from G3516 product line while minimizing changes to core diesel engine
    • Fully integrated diesel and gas controls into single engine control unit with single point operation for generator set and DGB system

    BENEFITS AND FEATURES

    Dynamic Gas Blending (DGB) System

    • Horizontally mounted radiator with vertical discharge with high efficiency fan
    • Provides 43C (110F) ambient capability
    • Variable frequency drive fan controls improve partial load fuel consumption
    • BENEFITS AND FEATURES

    Cat Cooling System

    • Provides auto paralleling using package mounted controls
    • EMCP 4.3 offers engine and generator monitoring and protection, including DGB enable and substitution level set points
    • AGC-4 provides paralleling, load sharing, VFD control, and primary generator protection

    BENEFITS AND FEATURES

    On-Package Paralleling Control System

    • 3 phase sensing and adjustable V/Hz regulation
    • Provides precise control, excellent block loading, and constant voltage in the normal operating range

    BENEFITS AND FEATURES

    Digital Voltage Regulator (Cat DVR)